This CT PT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard, include excitation data, saturation inflection point, remanence coefficient, accuracy limit overcurrent factor, ratio and error data. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button. It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.
Type
|
JHCTA-1812
|
|
Function
|
CT, PT
|
|
Output
|
0~180Vrms,12Arms,36A( Peak value )
|
|
Voltage measurement accuracy
|
±0.1%
|
|
CT ratio test
|
Range:1~40000 Accuracy:±0.05%
|
|
PT ratio test
|
Range:1~40000 Accuracy:±0.05%
|
|
Phase test
|
Accuracy:±5min Resolving power:0.5min
|
|
Secondary resistance test
|
Range:0~300Ω Accuracy:0.2%±2mΩ
|
|
AC burden test
|
Range:0~1000VA Accuracy:0.2%±0.02VA
|
|
Input voltage
|
AC220V±10%,50Hz
|
|
Work environment
|
Temperature :-10οC~50οC, Humidity :≤90%
|
|
Size/Weight
|
365 mm×290 mm×153mm, Weight:<10kg<>
|